Visible to the public Biblio

Filters: Keyword is exponentially decaying DC offset  [Clear All Filters]
2015-05-06
Zhen Jiang, Shihong Miao, Pei Liu.  2014.  A Modified Empirical Mode Decomposition Filtering-Based Adaptive Phasor Estimation Algorithm for Removal of Exponentially Decaying DC Offset. Power Delivery, IEEE Transactions on. 29:1326-1334.

This paper proposes a modified empirical-mode decomposition (EMD) filtering-based adaptive dynamic phasor estimation algorithm for the removal of exponentially decaying dc offset. Discrete Fourier transform does not have the ability to attain the accurate phasor of the fundamental frequency component in digital protective relays under dynamic system fault conditions because the characteristic of exponentially decaying dc offset is not consistent. EMD is a fully data-driven, not model-based, adaptive filtering procedure for extracting signal components. But the original EMD technique has high computational complexity and requires a large data series. In this paper, a short data series-based EMD filtering procedure is proposed and an optimum hermite polynomial fitting (OHPF) method is used in this modified procedure. The proposed filtering technique has high accuracy and convergent speed, and is greatly appropriate for relay applications. This paper illustrates the characteristics of the proposed technique and evaluates its performance by computer-simulated signals, PSCAD/EMTDC-generated signals, and real power system fault signals.