Visible to the public Biblio

Filters: Author is Amadis, Simon  [Clear All Filters]
2021-11-29
Silva-Saravia, Horacio, Singh, Iknoor, Chynoweth, Joshua, Mateo, Norbo, Mejia, Manuel, Amadis, Simon, Alvarez, Rufino.  2020.  Islanding Detection and Resynchronization Based upon Wide-Area Monitoring and Situational Awareness in the Dominican Republic. 2020 IEEE PES Transmission Distribution Conference and Exhibition - Latin America (T D LA). :1–6.
This paper shows the benefits of synchrophasor technology for islanding detection and resynchronization in the control room at Empresa de Transmisión Eléctrica Dominicana (ETED) in the Dominican Republic. EPG's Real Time Dynamics Monitoring System (RTDMS®) deployed at ETED was tested during operator training with the event data after an islanding event occurred on October 26, 2019, which caused the ETED System to split into two islands. RTDMS's islanding detection algorithm quickly detected and identified the event. The islanding situation was not clear for operators during the time of the event with the use of traditional SCADA tools. The use of synchophasor technology also provides valuable information for a quick and safe resynchronization. By monitoring the system frequency in each island and voltage angle differences between islands, operators can know the exact time of circuit breaker closure for a successful resynchronization. Synchrophasors allow the resynchronization in a relatively short time, avoiding the risk of additional load loss, generator outages or even a wider system blackout.