The risk of large-scale blackouts and cascading failures in power grids can be due to vulnerable transmission lines and lack of proper remediation techniques after recognizing the first failure. In this paper, we assess the vulnerability of a system using fault chain theory and a power flow-based method, and calculate the probability of large-scale blackout. Further, we consider a Remedial Action Scheme (RAS) to reduce the vulnerability of the system and to harden the critical components against intentional attacks. To identify the most critical lines more efficiently, a new vulnerability index is presented. The effectiveness of the new index and the impact of the applied RAS is illustrated on the IEEE 14-bus test system.
Transmission lines' monitoring systems produce a large amount of data that hinders faults diagnosis. For this reason, approaches that can acquire and automatically interpret the information coming from lines' monitoring are needed. Furthermore, human errors stemming from operator dependent real-time decision need to be reduced. In this paper a multiple faults diagnosis method to determine transmission lines' operating conditions is proposed. Different scenarios, including insulator chains contamination with different types and concentrations of pollutants were modeled by equivalents circuits. Their performance were characterized by leakage current (LC) measurements and related to specific fault modes. Features extraction's algorithm relying on the difference between normal and faulty conditions were used to define qualitative trends for the diagnosis of various fault modes.