Adversarial models are well-established for cryptographic protocols, but distributed real-time protocols have requirements that these abstractions are not intended to cover. The IEEE/IEC 61850 standard for communication networks and systems for power utility automation in particular not only requires distributed processing, but in case of the generic object oriented substation events and sampled value (GOOSE/SV) protocols also hard real-time characteristics. This motivates the desire to include both quality of service (QoS) and explicit network topology in an adversary model based on a π-calculus process algebraic formalism based on earlier work. This allows reasoning over process states, placement of adversarial entities and communication behaviour. We demonstrate the use of our model for the simple case of a replay attack against the publish/subscribe GOOSE/SV subprotocol, showing bounds for non-detectability of such an attack.
IEC 61850 is an international standard that is widely used in substation automation systems (SAS) in smart grids. During its development, security was not considered thus leaving SAS vulnerable to attacks from adversaries. IEC 62351 was developed to provide security recommendations for SAS against (distributed) denial-of-service, replay, alteration, spoofing and detection of devices attacks. However, real-time communications, which require protocols such as Generic Object-Oriented Substation Event (GOOSE) to function efficiently, cannot implement these recommendations due to latency constraints. There has been researching that sought to improve the security of GOOSE messages, however, some cannot be practically implemented due to hardware requirements while others are theoretical, even though latency requirements were met. This research investigates the possibility of encrypting GOOSE messages with One- Time Pads (OTP), leveraging the fact that encryption/decryption processes require the random generation of OTPs and modulo addition (XOR), which could be a realistic approach to secure GOOSE while maintaining latency requirements. Results show that GOOSE messages can be encrypted with some future work required.
Electrical substations are crucial for power grids. A number of international standards, such as IEC 60870 and 61850, have emerged to enable remote and automated control over substations. However, owing to insufficient security consideration in their design and implementation, the resulting systems could be vulnerable to cyber attacks. As a result, the modernization of a large number of substations dramatically increases the scale of potential damage successful attacks can cause on power grids. To counter such a risk, one promising direction is to design and deploy an additional layer of defense at the substations. However, it remains a challenge to evaluate various substation cybersecurity solutions in a realistic environment. In this paper, we present the design and implementation of SoftGrid, a software-based smart grid testbed for evaluating the effectiveness, performance, and interoperability of various security solutions implemented to protect the remote control interface of substations. We demonstrate the capability and usefulness of SoftGrid through a concrete case study. We plan to open-source SoftGrid to facilitate security research in related areas.
This paper proposes a new network-based cyber intrusion detection system (NIDS) using multicast messages in substation automation systems (SASs). The proposed network-based intrusion detection system monitors anomalies and malicious activities of multicast messages based on IEC 61850, e.g., Generic Object Oriented Substation Event (GOOSE) and Sampled Value (SV). NIDS detects anomalies and intrusions that violate predefined security rules using a specification-based algorithm. The performance test has been conducted for different cyber intrusion scenarios (e.g., packet modification, replay and denial-of-service attacks) using a cyber security testbed. The IEEE 39-bus system model has been used for testing of the proposed intrusion detection method for simultaneous cyber attacks. The false negative ratio (FNR) is the number of misclassified abnormal packets divided by the total number of abnormal packets. The results demonstrate that the proposed NIDS achieves a low fault negative rate.
Critical Infrastructure represents the basic facilities, services and installations necessary for functioning of a community, such as water, power lines, transportation, or communication systems. Any act or practice that causes a real-time Critical Infrastructure System to impair its normal function and performance will have debilitating impact on security and economy, with direct implication on the society. SCADA (Supervisory Control and Data Acquisition) system is a control system which is widely used in Critical Infrastructure System to monitor and control industrial processes autonomously. As SCADA architecture relies on computers, networks, applications and programmable controllers, it is more vulnerable to security threats/attacks. Traditional SCADA communication protocols such as IEC 60870, DNP3, IEC 61850, or Modbus did not provide any security services. Newer standards such as IEC 62351 and AGA-12 offer security features to handle the attacks on SCADA system. However there are performance issues with the cryptographic solutions of these specifications when applied to SCADA systems. This research is aimed at improving the performance of SCADA security standards by employing NTRU, a faster and light-weight NTRU public key algorithm for providing end-to-end security.
The reliability theory used in the design of complex systems including electric grids assumes random component failures and is thus unsuited to analyzing security risks due to attackers that intentionally damage several components of the system. In this paper, a security risk analysis methodology is proposed consisting of vulnerability analysis and impact analysis. Vulnerability analysis is a method developed by security engineers to identify the attacks that are relevant for the system under study, and in this paper, the analysis is applied on the communications network topology of the electric grid automation system. Impact analysis is then performed through co-simulation of automation and the electric grid to assess the potential damage from the attacks. This paper makes an extensive review of vulnerability and impact analysis methods and relevant system modeling techniques from the fields of security and industrial automation engineering, with a focus on smart grid automation, and then applies and combines approaches to obtain a security risk analysis methodology. The methodology is demonstrated with a case study of fault location, isolation and supply restoration smart grid automation.